BESS & Microgrids · Lesson 3 of 5

Sizing from interval data and dispatch behavior

Monthly energy totals hide the shape that storage must control. Two facilities can consume the same monthly kWh while one has a sharp fifteen-minute demand peak and the other has a flat profile. Peak shaving depends on the magnitude, timing and duration of the peak; resilience depends on the selected load and outage duration; solar shifting depends on simultaneous generation and demand.

15minutes3learning objectives3check questions
LEARNING OBJECTIVES

After this lesson, you should be able to:

  1. Use interval load data rather than monthly consumption alone
  2. Connect dispatch logic to power and energy requirements
  3. State efficiency, reserve and degradation assumptions transparently
EXPLANATION

What is physically and operationally happening?

Monthly energy totals hide the shape that storage must control. Two facilities can consume the same monthly kWh while one has a sharp fifteen-minute demand peak and the other has a flat profile. Peak shaving depends on the magnitude, timing and duration of the peak; resilience depends on the selected load and outage duration; solar shifting depends on simultaneous generation and demand.

A credible sizing model replays a defined dispatch rule against interval data. It applies charger and discharge limits, SOC bounds, efficiency, auxiliary consumption, reserve and degradation. The result is not one magical size but a comparison of feasible configurations, missed targets and sensitivity to assumptions.

01

Load profile

Validated interval demand reveals peaks, duration, variability and critical-load behavior.

kW by time
02

Dispatch rule

A defined algorithm charges, discharges and preserves reserve.

Setpoint
03

SOC model

Energy balance applies efficiency, limits and auxiliary loads each interval.

% SOC
04

Sensitivity

Tariff, degradation, outages and operating changes test decision robustness.

Range of outcomes
TECHNICAL VISUAL · SYSTEM-SPECIFIC MODEL

Illustrative peak-shaving dispatch

The BESS discharges above a site limit and may recharge when headroom is available.

ENGINEERING VIEW · ILLUSTRATIVE

Sizing and dispatch evidence profile

%
Observed chainReference trend

Site demand and target limit. Values are educational, not Metro Power project-performance claims.

READING NOTEIllustrative normalized load curve. Replace with validated interval data, tariff periods and exact equipment constraints.
OPTIONAL ENGINEERING DEPTHSizing evidenceUse interval load, tariff, outages, critical loads, generation and efficiency assumptions.
DESIGN RELATIONSHIPRequired nominal energy = delivered energy ÷ (efficiency × usable SOC window × end-of-life factor)
  • Separate PCS power from battery energy
  • Resolve reserve versus commercial dispatch priority
  • Include losses, degradation, auxiliaries and downtime
ENGINEERING CHECKS FOR THIS LESSON
  1. 01Simulate the complete interval sequence and SOC
  2. 02Coordinate BMS, PCS, EMS, protection and transformer states
  3. 03Test tariff, warranty and availability sensitivities
FAILURE ANALYSIS
Observed signalPossible causeDiscriminating test

Peak cap fails during long events

Energy depletes despite sufficient PCS power

Replay interval load and SOC

Outage reserve is unavailable

Commercial dispatch consumed reserved energy

Compare command history with EMS policy

PROJECT EVIDENCE TO COLLECT
  • Interval load and generation data
  • Dispatch and SOC simulation
  • Approved one-line, controls and protection basis
WORKED EXAMPLE

Energy needed to cap a peak

Demand exceeds a 700 kW limit for three intervals: 820 kW, 940 kW and 780 kW, each 15 minutes.

  1. Required powers are 120, 240 and 80 kW
  2. Energy = (120 + 240 + 80) × 0.25 h = 110 kWh
  3. Maximum discharge power is 240 kW
  4. Then add losses, reserve, degradation and repeat across the full data period
INTERPRETATION

The use case needs at least 240 kW power and more than 110 kWh usable energy for this event, but annual sizing requires the complete interval series.

COMMON FAILURE OR MISCONCEPTION
The monthly bill is enough to size a demand-management BESS.

Monthly kWh and even billed peak do not reveal the shape, duration and recurrence that determine power, energy and recharge behavior.

RETRIEVAL PRACTICE · 3 QUESTIONS

Check what you can explain without looking back.

Choose an answer and report your confidence. The confidence signal is stored only until you submit this page.

OBJECTIVE · Choose data

What is most important for peak-shaving simulation?

How confident are you?
OBJECTIVE · Calculate energy

A 200 kW discharge lasts 30 minutes. Delivered energy is:

How confident are you?
OBJECTIVE · State assumptions

Which assumptions affect usable delivered energy?

How confident are you?
Answer every question and confidence prompt.